
Class A office tower
Midtown, New York City
504,500 SF
$109,376saved per year

Most buildings heat and cool far more outdoor air than code requires. Poppy measures what every zone actually receives, then helps you cut the excess. No upfront cost. No retrofits.
In 198 Class A office tests, buildings were over-ventilating by 2-2.5x on average.
Few buildings know how much outdoor air actually reaches each zone. On every floor, the real number is a question mark.
At 95°F, every extra cubic foot of outdoor air needs cooling. At 10°F, it needs heating. No alerts. No warnings. Just a higher utility bill.
Step one: a Poppy sensor goes on the outdoor air intake, where your building breathes in. It logs the outdoor CO₂ entering the system.
Battery powered. No BMS, no Wi-Fi, no equipment connection. Patent pending.
Each key zone gets its own battery powered Poppy sensor, logging indoor CO₂ where people work. The intake and the zones are read side by side.
Outside, CO₂ rises and falls every day. Cars add it. Trees and plants remove it. Indoors, the same cycle arrives late, and the delay depends on how much outdoor air the zone receives. DVM reads that delay, zone by zone, around the clock. Measured, not modelled.
Outdoor air delivered to each zone, against its ASHRAE 62.1 target: under code, on target or over code.
Assess. Optimize. Maintain.
Verified results

Class A office tower
504,500 SF
$109,376saved per year

Retail center · Highest-return property
250,000 SF
$377,260saved per year

Regional mall · Phase 1, 26 AHUs
1,633,000 SF
$28,797saved per year

Multi-tenant office · Cross-border delivery
185,000 SF
$21,000saved per year
Where Poppy works
Typically 100,000+ sq ft, with mechanical outdoor air.

Why Poppy
All we do is optimize ventilation. Not a broad energy consultancy. Not an equipment vendor. One thing, and no one has tested more buildings to prove it.
Trusted by the world's leading property owners and operators
"Poppy reduced our outdoor air load by 46% while keeping healthy CO₂ levels. The reporting keeps our team informed without any manual effort."
"Indoor air quality scores improved, ventilation energy costs fell by 22%, and none of it required a capital spend."
"We were sceptical that you could cut HVAC spend without compromising air quality. The verified savings removed every doubt. This is now standard in our portfolio."
Aligned with leading standards
LEED v5
Fitwel
ASHRAE 62.1 and 241
Compatibility
DVM measures the outdoor air that actually reaches each zone, whatever equipment delivers it.
Scroll or choose your system
Dedicated outdoor air
A dedicated outdoor air system: 100% outdoor air, sized for ventilation only. Separate equipment heats and cools.
The simplest case. The OA path is explicit, and DVM measures the CFM reaching each zone.
Qualifies
Built-up air handler
The mixing box blends outdoor and return air through OA, return and relief dampers, then feeds VAV boxes. Damper position sets the OA fraction.
DVM measures the outdoor air each zone receives after mixing.
Qualifies
Packaged
Return and outdoor air mix through the intake-hood damper. The minimum position is set once at startup and rarely revisited.
Highest-value application for DVM. Exception: some small RTUs ship with no OA hood.
QualifiesHighest value
Packaged
Common in classrooms, schools and floor-by-floor systems. Built with an OA damper and a louver or OA duct.
Measured the same way as an RTU.
Qualifies
Packaged
Through-wall units in hotels and senior living. The OA vent door is often closed or blocked.
Usually marginal on its own. If a DOAS or makeup air unit ventilates the building, Poppy measures that system.
MarginalQualifies via DOAS
Recirculation systems
Recirculation only. Any outdoor air comes from a separate DOAS or ventilation unit.
With a DOAS: qualifies. Without one, there is no mechanical ventilation to measure.
Qualifies via DOAS
No outdoor air path
Split systems, closed-vent PTACs and fan coils with no OA duct recirculate indoor air only.
No outdoor air rate to measure or optimize.
Does not qualify

Start with a no cost 2-week DVM assessment. Find out where your building stands today, zone by zone.
We only win when you win: no upfront cost, no capital, no retrofits.